(Asia Only)
|
|
|
|
GT-540-3GWA |
|
|
|
|
|
|
|
|
|
GT-540-3GWA is an intelligent Active 3G Remote Terminal Unit. Within the high performance 32 bit CPU, GT-540-3GWA is suit for the hard industrial environment. It features 3G(WCDMA) module, 6 digital inputs, 2 digital outputs, 1 analog input, 1 RS-232, 1 RS-485 and SD interface. It can be used in M2M application fields to transfer the local I/O or Modbus device's data via GPRS by the defined period or DI/AI triggers. The local I/O data can also be stored in the SD card to become a remote data logger. For another communication path, GT-540-3GWA offers the e-mail mode to transfer the data by e-mail via 3G for users to choose. The simple I/O linkage function of GT-540-3GWA can reach the real time control in local field. It also supports Li-ion battery as another power source when the main power is failed temporarily. Therefore, GT-540-3GWA is an ideal solution for environmental monitoring and remote device management for M2M applications. Meanwhile, it is supplied with easy-to-use API and OPC server Software that streamline application development process, freeing system integrators from dealing with complex communication protocols of 3G and the Internet.
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
- Automatic/continuous WCDMA/GPRS Link Management
- Support Modbus RTU protocol to connect to Max 3 Modbus RTU devices via RS-485 port
- Support M2M OPC server for SCADA system
- Easy-to-use API tool for users to develop their applications by various program development tools
- Be the WCDMA/GPRS I/O devices
- Local I/O linkage function to make the simple local control
- Support 3.7V Li-ion Battery backup
- Power supply 10 ~ 30 VDC
|
|
|
|
|
|
|
|
ICP DAS provide graphic tool for users to configure GT-540-3GWA. The utility also can help users to test GT-540-3GWA in the Lab before they apply in the real site.
|
|
|
|
|
|
|
|
The M2M RTU center software with friendly Graphic interface is to manage the WCDMA/GPRS RTU products easily. Users can monitor the I/O data and status of WCDMA/GPRS RTU devise by the interface on PC. By using the M2M RTU API tool and M2M RTU center software, any remote monitoring system can be achieved easily and efficiently. For SCADA system, the M2M.OPC server is provided to connect to SCADA by OPC interface.
Item |
Web site |
M2M RTU Center |
|
M2M RTU Win32 API |
|
NAPOPC.M2M DA Server |
|
EZ Data Logger |
|
InduSoft SCADA |
|
-
Easy to Establish WCDMA/GPRS Network Applications
It is a big headache for engineers to establish the WCDMA/GPRS applications because the dynamic IP management is required. Applying GT-540-3GWA and M2M RTU center software, the dynamic IP addresses can be managed between them. The remote WCDMA/GPRS RTU product would connect to M2M RTU Center automatically. Therefore, all remote WCDMA/GPRS RTU devices can be managed by s single centralized M2M RTU Center software with a fixed IP address. Moreover, there are M2M API tool and OPC server for engineers to develop the WCDMA/GPRS applications by VB, VC or SCADA development tools conveniently without any IP address management effort.
-
Active data transmission
GT-540-3GWA with active I/O transmission mechanism can raise the communication. Unlike the traditional poll communication, it would transfer the data by the defined time, DI trigger or AI hi/lo alarm. In addition to improve the way of communication, that can also reduce the AP effort.
-
Transfer data by e-mail
Expect for the transferring data by the general communication with the M2M RTU center, users can choose the e-mail mode to send these data by e-mail over WCDMA/GPRS in the fixed time.
-
Modbus RTU device connectivity
GT-540-3GWA is built-in Modbus RTU protocol. That can make any Modbus RTU device connect to GT-540-3GWA. By the way of GT-540-3GWA, Modbus RTU devices can be used in WCDMA/GPRS remote system. The max Modbus RTU device can be connected to GT-540-3GWA is three.
-
Simple Local I/O link Control
There are I/O built-in WCDMA/GPRS devices of ICP DAS. Therefore, these products can be the WCDMA/GPRS I/O devices. Expect for these local I/O data can be sent to the host PC, the I/O link function of them help users to do the simple control in local field. For example: the DI trigger or high/low AI alarm can driver the DO channel.
-
Built-in I/O Data Logging
GT-540-3GWA provides an external SD interface. These local I/O and Modbus data are recorded in SD memory card for one day in a single file.
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
System |
CPU |
32 bit CPU |
SRAM |
64 Kbytes |
Flash Memory |
512 Kbytes |
RTC |
Gives time(sec, min, hour) & date, leap year compensation from 1980 to 2079 |
WDT(watchdog) |
Yes |
SD interface |
4GB max. |
Serial ports |
COM1 |
RS-232 : TxD,RxD,GND for configuration |
COM2 |
RS-485 : D2+, D2- for modbus device |
Digital Input |
Input Channel |
6 |
Input Type |
Sink or Source, Isolated channel with common power or ground |
Off Voltage Level |
+1V max. |
On Voltage Level |
+3.5 ~ 30 VDC |
Isolated Voltage |
3750Vrms |
Counters |
6 (5~40Hz), Min. Pulse Width : 25ms |
Digital Output |
Channels |
2 |
Output Type |
Open-Collector (NPN) (100mA@30VDC) |
Load Voltage |
+30 V max. |
Load Current |
100 mA max. |
Isolated Voltage |
3750Vrms |
Analog Input |
Channels |
1 |
Resolution |
12 bit |
Input Range/Type |
0 ~ 20 mA |
2G system |
GPRS/GSM |
Quad-band 850/900/1800/1900 MHz
GPRS multi-slot : class 10/8
GPRS mobile station : class B
Compliant to GSM phase 2/2+
- Class 4(2W @ 900 MHz)
- Class 1(1W @ 1800/1900 MHz)
Coding schemes : CS 1, CS 2,CS 3,CS 4 |
3G System |
Frequency Band |
WCDMA : 850/900/1900/2100 MHz |
Power class |
Class 3(250mW @ WCDMA/HSPA) |
Power |
Protection |
Reverse polarity protection |
Frame Ground Protection |
ESD, Surge, EFT, Hi-Pot |
Required Supply Voltage |
+10 VDC ~ +30 VDC |
Power Consumption |
Idle: 65 mA @ 24 VDC; Data Link: 170 mA @ 24 VDC; Peak: 450 mA @ 24 VDC |
Mechanical |
Casing |
Plastic |
Flammability |
UL 94V-0 materials |
Dimensions (W x L x H) |
91 mm x 132 mm x 52 mm |
Installation |
DIN-Rail |
Environmental |
Operating Temperature |
-25 ℃ ~ +75 ℃ |
Storage Temperature |
-40 ℃ ~ +80 ℃ |
Ambient Relative Humidity |
5 ~ 95% RH, non-condensing |
|
|
|
|
|
|
|
|
GT-540-3GWA CR |
Intelligent 3G Remote Terminal Unit (RoHS) (Asia Only) |
|
For quotation ; For product information ; For project or solution discussion |
|
|
|
|
|
|
|
|
|
5 dBi 4G External Antenna (Support 3G/4G)
|
|
Battery Box (RoHS) |
|
|
|
|
|